Magnetic ac contactor JLC1-09/12
Uri ng Pagtatalaga

Teknikal na Parameter
Midel | 2 Cable cross Section(cu) | Laki ng tornilyo | Tighteningtorque(N. m) | |||
Bilang ng piraso | Flexible na cable na may cold-prossed socKet(mm2) | Flexible na cable na walang cold-pressed socket(mm2) | lnflekible cable(mm2) | |||
JLC1-09 | 1-2 | 2.5 | 4 | 4 | M3.5 | 0.8 |
JLC1-12 | 1-2 | 2.5 | 4 | 4 | M3.5 | 0.8 |
JLC1-18 | 1-2 | 4 | 6 | 6 | M3.5 | 0.8 |
JLC1-25 | 1 | 4 | 10 | 6 | M4 | 1.2 |
2 | 4 | 6 | 6 | M4 | 1.2 | |
JLC1-32 | 1 | 4 | 10 | 6 | M4 | 1.2 |
2 | 4 | 6 | 6 | M4 | 1.2 | |
JLC1-40 | 1 | 10 | 16 | 10 | M4 | 3.5 |
2 | 10 | 10 | 10 | M8 | 3.5 | |
JLC1-50 | 1 | 16 | 25 | 25 | M8 | 3.5 |
2 | 16 | 16 | - | M8 | 3.5 | |
JLC1-65 | 1 | 16 | 25 | 25 | M8 | 3.5 |
2 | 16 | 16 | - | M8 | 3.5 | |
JLC1-80 | 1 | 50 | 50 | 50 | M8 | 3.5 |
2 | 25 | 35 | - | M10 | 4.0 | |
JLC1-95 | 1 | 50 | 20 | 50 | M10 | 4.0 |
2 | 25 | 35 | - | M10 | 4.0 |
Pangkalahatang Mga Dimensyon at Pag-mount (mm)

Mga sitwasyon ng aplikasyon:
Karaniwang naka-install sa distribution box sa sahig, computer center, telecommunication room, elevator control room, cable TV room, building control room, fire center, industrial automatic control area, hospital operation room, monitoring room at distribution box equipment na may elektronikong kagamitang medikal .