Thermal Overload Relay JLR2-D13
Katangian ng Paggalaw: Three-phase Balance Motion Time
No | Mga oras ng kasalukuyang setting(A) | Oras ng paggalaw | Simulan ang kundisyon | Temperatura sa paligid | ||
1 | 1.05 | >2h | Malamig na estado | 20±5°C
| ||
2 | 1.2 | <2h | Estado ng init | |||
3 | 1.5 | <4min | (Kasunod ng No.l test) | |||
4 | 7.2 | 10A | 2s | <63A | Malamig na estado | |
10 | 4s | >63A |
Phase-losing Motion Characteristic
No | Mga oras ng kasalukuyang setting(A) | Oras ng paggalaw | Simulan ang kundisyon | Temperatura sa paligid | |
Anumang dalawang yugto | Isa pang yugto | ||||
1 | 1.0 | 0.9 | >2h | Malamig na estado | 20±5°C |
2 | 1.15 | 0 | <2h | Estado ng init (Kasunod ng No.l test) |
Pagtutukoy
Uri | Numero | Saklaw ng pagtatakda (A) | Para sa contactor |
JLR2-D13
| 1301 | 0.1~0.16 | JLC1-09~32 |
1302 | 0.16~0.25 | JLC1-09~32 | |
1303 | 0.25~0.4 | JLC1-09~32 | |
1304 | 0.4~0.63 | JLC1-09~32 | |
1305 | 0.63~1 | JLC1-09~32 | |
1306 | 1~1.6 | JLC1-09~32 | |
1307 | 1.6~2.5 | JLC1-09~32 | |
1308 | 2.5~4 | JLC1-09~32 | |
1310 | 4~6 | JLC1-09~32 | |
1312 | 5.5~8 | JLC1-09~32 | |
1314 | 7~10 | JLC1-09~32 | |
1316 | 9~13 | JLC1-09~32 | |
1321 | 12~18 | JLC1-09~32 | |
1322 | 17~25 | JLC1-32 | |
JLR2-D23
| 2353 | 23~32 | CJX2-09~32 |
2355 | 30~40 | JLC1-09~32 | |
JLR2-D33
| 3322 | 17~25 | JLC1-09~32 |
3353 | 23~32 | JLC1-09~32 | |
3355 | 30~40 | JLC1-09~32 | |
3357 | 37~50 | JLC1-09~32 | |
3359 | 48~65 | JLC1-09~32 | |
3361 | 55~70 | JLC1-09~32 | |
3363 | 63~80 | JLC1-09~32 | |
3365 | 80~93 | JLC1-95 | |
JLR2-D43
| 4365 | 80~104 | JLC1-95 |
4367 | 95~120 | JLC1-95~115 | |
4369 | 110~140 | JLC1-115 |
Balangkas at Dimensyon ng Pag-mount
Mga accessories
Mga sitwasyon ng aplikasyon:
Karaniwang naka-install sa distribution box sa sahig, computer center, telecommunication room, elevator control room, cable TV room, building control room, fire center, industrial automatic control area, hospital operation room, monitoring room at distribution box equipment na may electronic medical device .